LEESON
Variable Speed AC Motor Drives
RUN 60.00 HZ
PROG
RUN
AUTO
MAN
START
ENTER
FWD
REV
STOP
Micro Series
Quick Reference Guide
NOTE: Before installing and operating the MICRO SERIES
drive, please read and become familiar with the MICRO SERIES
Installation and Operation Manual.
Adjustable Speed AC Motor Control
2 OUTPUT ACCEL
In the example above, the second fault is being viewed, which is
an OUTPUT fault that occurred while the drive was accelerating.
FAULT
NUMBER
FAULT
MESSAGE
DRIVE
STATUS
MICRO SERIES FAULT HISTORY
Parameter 70 — FAULT HISTORY stores the last eight faults that
tripped the drive. The FAULT HISTORY indicates the number of
the fault (number 1 is the most recent fault), the fault message,
and the status of the drive at the time of the fault. An example is
shown below:
FAULT DESCRIPTION
OUTPUT Output Transistor fault. Output current exceeded 200%.
May be ground fault or short circuit.
LO VOLTS Low DC Bus Voltage fault. DC bus voltage dropped below 60%
May be low line voltage.
HI VOLTS High DC Bus Voltage fault. DC Bus voltage exceeded 120%.
May be overhauling load .
HI TEMP High Temperature fault. Heatsink or ambient temperature
too high.
OVERLOAD Current Overload fault. Output current exceeded 100% for
too long. VFD may be undersized.
PWR TRAN Power Transient fault.
PWR SAG Power Sag fault: New control board installed. Perform
factory reset using Parameter 65.
LANGUAGE Language EEPROM fault.
EXTERNAL External fault: TB-130 activated (Parameter 50).
DB ERROR Dynamic Brake fault. DB Resistors overloaded.
CONTROL Control Board fault. New solfware installed. Perform factory
reset using Parameter 65.
INTERNAL Internal fault
INTERN (#) Internal fault.
MC3000 FAULT MESSAGES
PARAMETER FACTORY PARAMETER FACTORY
NO. NAME DEFAULT NO. NAME DAFAULT
0 LINE VOLTS AUTO
1 SPEED #1 20.00 Hz
2 SPEED #2 20.00 Hz
3 SPEED #3 20.00 Hz
4 SPEED #4 20.00 Hz
5 SKIP #1 .00 Hz
6 SKIP #2 .00 Hz
7 BAND WID 1.00 Hz
8 ACCEL 30.0 SEC
9 DECEL 30.0 SEC
10 MIN FRQ .50 Hz
11 MAX FRQ 60.00 Hz
12 DC BRAKE .0 VDC
13 DC TIME .0 SEC
14 DYN BRAKE OFF
16 CURRENT 180%
17 MOTOR OL 100%
18 BASE 60.00 Hz
19 FX BOOST (NOTE 1)
20 AC BOOST .0%
21 SLIP COMP .0%
22 TORQUE CONSTANT
23 CARRIER 2.5 kHz
25 START NORMAL
26 STOP COAST
27 ROTATION FORWARD
28 AUTO/MAN BOTH
29 MANUAL KEYPAD
30 CONTROL LOCAL
31 UNITS HERTZ
32 HZ MULT 1
33 UNITS DP XXXX
34 LOAD MLT 100%
35 CONTRAST HIGH
39 TB5 MIN .00 Hz
40 TB5 MAX 60.00 Hz
42 TB10A OUT NONE
43 @TB10A 60.00 Hz
44 TB10B OUT NONE
45 @TB10B 125%
47 TB13A NONE
48 TB13B NONE
49 TB13C NONE
50 TB13D FAULT
52 TB14 OUT NONE
53 TB15 OUT NONE
54 RELAY NONE
58 ADDRESS 30
61 PASSWORD 0019
63 SOFTWARE (NOTE 2)
64 MONITOR ON
65 PROGRAM RESET 60
66 HISTORY MAINTAIN
70 FAULT HIST. (NOTE 2)
NOTE 1: REFER TO THE MICRO SERIES MANUAL.
NOTE 2: THESE PARAMETERS ARE VIEW-ONLY.
MICRO SERIES PARAMETERS
Micro Series
Intelligent Drive
Digital
LEESON SPEEDMASTER
BULLETIN #2452 3/98
Page view 0
1 2

Summary of Contents

Page 1 - Quick Reference Guide

LEESONVariable Speed AC Motor DrivesRUN 60.00 HZPROGRUNAUTOMANSTARTENTERFWDREVSTOPMicro SeriesQuick Reference GuideNOTE: Before installing and opera

Page 2 - MICRO SERIES KEYPAD

STOP 20.00 HZPROGRUNAUTOMANSTARTENTERFWDREVSTOPPress the START key to start the drive. The START keyis only active in LOCAL mode.PROGRAMMING THE MIC

Comments to this Manuals

No comments